PROFIBUS OLM/G11-1300 V4.0 |
|
PROFIBUS OLM/G11-1300V4.0 optical link module with 1 RS485 and 1 glass FOC interface (2 BFOC- sockets), 1300 Nm shaft Length for large distances with signaling contact and test port |
Transmission rate |
Transfer rate / with PROFIBUS |
9.6 kbit/s ... 12 Mbit/s |
Transfer rate / with PROFIBUS PA |
45.45 kbit/s |
Interfaces |
Number of electrical/optical connections / for network components or terminal equipment / maximum |
2 |
Number of electrical connections |
|
● for network components or terminal equipment |
1 |
● for measuring device |
1 |
● for signaling contact |
1 |
● for power supply |
1 |
● for redundant voltage supply |
1 |
Type of electrical connection |
|
● for network components or terminal equipment |
9-pin Sub-D socket |
● for measuring device |
2-pole terminal block |
● for power supply and signaling contact |
5-pole terminal block |
Number of optical interfaces / for fiber optic cable |
1 |
Design of the optical interface / for fiber optic cable |
BFOC port |
Optical data |
Damping ratio / of the FOC transmission link |
|
● for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km / maximum |
8 dB |
propagation delay [bit] |
6.5 bit |
Connectable optical power relative to 1 mW |
|
● for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km |
-19 dB |
Optical sensitivity relating to 1 mW |
|
● for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km |
-29 dB |
Wavelength |
|
● for glass FOC with 10/125 µm or 9/125 µm / compatible with interface / at 0.5 dB/km |
1310 nm |
Wire length |
|
● for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km / maximum |
15 km |