6ES7350-1AH03-0AE0 SIMATIC S7-300, COUNTER MODULE
SIMATIC S7-300, COUNTER MODULE FM 350-1 FOR S7-300, COUNTER FUNCTIONS UP TO 500 KHZ 1 CHANNEL FOR CONNECTION OF 5V AND 24V INCREMENTAL ENCODERS ISOCHRON MODE, MEASUREMENT MODE INCL. CONFIG. PACKAGE ON CD
Supply voltage |
Auxiliary voltage 1L+, load voltage 2L+ |
● Rated value (DC) |
24 V |
Permissible range (ripple included) |
— dynamic, lower limit (DC) |
18.5 V |
— dynamic, upper limit (DC) |
30.2 V |
— static, lower limit (DC) |
20.4 V |
— static, upper limit (DC) |
28.8 V |
non-periodic skip |
— Duration |
500 ms |
— Recovery time |
50 s |
— Value |
35 V |
Input current |
from load voltage 1L+ (without load), max. |
40 mA |
from backplane bus 5 V DC, max. |
160 mA |
Encoder supply |
5 V encoder supply |
● 5 V |
Yes; 5.2 V +/-2% |
● Output current, max. |
300 mA |
24 V encoder supply |
● 24 V |
Yes; 1L+ (-3 V) |
● Output current, max. |
400 mA |
Power loss |
Power loss, typ. |
4.5 W |
Digital inputs |
Number of digital inputs |
3 |
Functions |
1 for gate start, 1 for gate stop, 1 for setting the counter |
Input voltage |
● for signal "0" |
-28.8 ... +5V |
● for signal "1" |
+11 to +28.8V |
Input current |
● for signal "1", typ. |
9 mA |
Digital outputs |
Number of digital outputs |
2 |
Short-circuit protection |
Yes; Clocked electronically |
Limitation of inductive shutdown voltage to |
2L+ (-39 V) |
Output voltage |
● for signal "0", max. |
3 V |
● for signal "1", min. |
2L+ (-1,5 V) |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range for 0 to 60 °C, min. |
5 mA |
● for signal "1" permissible range for 0 to 60 °C, max. |
0.6 A |
Output delay with resistive load |
● "0" to "1", max. |
300 µs |
Encoder |
Connectable encoders |