6ES7222-1EF22-0XA0 EM222, 8DO, AC 120/230V, 0.5A, OPT.ISOL.
SIMATIC S7-200, DIGITAL OUTPUT EM 222, OPTICALLY ISOLATED 8DQ, 120/230V AC, 0.5A
Supply voltage |
Load voltage L1 |
● Rated value (AC) |
230 V; 220/230 V AC |
● permissible range, lower limit (AC) |
65 V |
● permissible range, upper limit (AC) |
264 V |
● permissible frequency range, lower limit |
47 Hz |
● permissible frequency range, upper limit |
63 Hz |
Input current |
from backplane bus 5 V DC, max. |
110 mA |
Power loss |
Power loss, typ. |
4 W |
Digital outputs |
Number of digital outputs |
8 |
Short-circuit protection |
No |
Limitation of inductive shutdown voltage to |
to be provided externally (see manual package "Setting up an S7-200") |
Output voltage |
● for signal "1", min. |
L1 (-0.9 V) |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range for 0 to 55 °C, max. |
500 mA; AC |
● for signal "1" minimum load current |
50 mA |
● for signal "0" residual current, max. |
1.8 mA; at 264 V AC |
Total current of the outputs (per group) |
all mounting positions |
— up to 40 °C, max. |
0.5 A |
— Current per conductor/group, max. |
0.5 A |
horizontal installation |
— up to 55 °C, max. |
0.5 A |
Relay outputs |
Switching capacity of contacts |
— with inductive load, max. |
0.5 A |
— on lamp load, max. |
60 W |
— with resistive load, max. |
0.5 A |
Cable length |
● shielded, max. |
500 m |
● unshielded, max. |
150 m |
Potential separation |
Potential separation digital outputs |
● Potential separation digital outputs |
Yes; Optocoupler |
● between the channels, in groups of |
1; 8 groups |