SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DO HIGH FEATURE 24V DC, 15 MM WIDTH DIAGNOSIS F. SHORT-CIRCUIT AND OPEN-CIRCUIT, FIRST-UP SIGNAL WITH LED SF (GROUP FAULT), 5 PIECES PER PACKAGING UNIT
Supply voltage |
Reverse voltage protection |
Yes; when using the same load voltage as on the power module |
Load voltage L+ |
● Rated value (DC) |
24 V; From power module |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
5 mA; Per channel |
from backplane bus 3.3 V DC, max. |
10 mA |
Power loss |
Power loss, typ. |
0.4 W |
Address area |
Address space per module |
● with packing |
2 bit |
● without packing |
1 byte |
Digital outputs |
Number of digital outputs |
2 |
Short-circuit protection |
|
● Response threshold, typ. |
1,5 A |
Limitation of inductive shutdown voltage to |
-55 to -60 V |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● on lamp load, max. |
2.5 W |
Load resistance range |
● lower limit |
48 Ω |
● upper limit |
3 400 Ω |
Output voltage |
● for signal "1", min. |
L+ (-1 V) |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "0" residual current, max. |
0.3 mA |
Output delay with resistive load |
● "0" to "1", max. |
100 µs |
● "1" to "0", max. |
400 µs |
Parallel switching of two outputs |
● for uprating |
No |
● for redundant control of a load |
Yes; per module |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
2 Hz |
● on lamp load, max. |
10 Hz |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Diagnostic functions |