6ES7350-2AH00-0AE0 FM350-2, COUNTER MOD. 8 CHANNELS, 20KHZ
SIMATIC S7-300, COUNTER MODULE FM 350-2, 8 CHANNELS, 20 KHZ, 24V ENCODER FOR COUNTING, MEASURING FREQUENCIES, SPEED MEASUREMENT, PERIOD DURATION MEASUREMENT AND PROPORTIONING INCL. CONFIG. PACKAGE AND ELECTRONIC DOCU ON CD
Supply voltage |
Auxiliary voltage 1L+, load voltage 2L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Input current |
from load voltage L+ (without load), max. |
150 mA |
from backplane bus 5 V DC, max. |
100 mA |
Encoder supply |
Type of output voltage |
NAMUR-encoder supply: 8.2 V +/-2% |
Short-circuit protection |
Yes |
Output current |
● Rated value |
200 mA |
Power loss |
Power loss, typ. |
10 W |
Digital inputs |
Number of digital inputs |
8 |
Functions |
1 each for gate start/ gate stop |
Input voltage |
● for signal "0" |
-3 to +5V |
● for signal "1" |
11 to 30.2 V |
Input current |
● for signal "0", max. (permissible quiescent current) |
2 mA |
● for signal "1", typ. |
9 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", max. |
50 µs |
Cable length |
● shielded, max. |
100 m |
Digital outputs |
Number of digital outputs |
8 |
Short-circuit protection |
Yes |
Limitation of inductive shutdown voltage to |
L+ (-40 V) |
Output voltage |
● for signal "1", min. |
L+ (-0.8 V) |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "0" residual current, max. |
0.5 mA |
Output delay with resistive load |
● "0" to "1", max. |
300 µs |
Switching frequency |
● with resistive load, max. |
500 Hz |
● with inductive load, max. |
0.5 Hz |
Total current of the outputs (per group) |
horizontal installation |
— up to 40 °C, max. |
4 A |
— up to 60 °C, max. |
2 A |
all other mounting posi
|