BC9000 - BECKHOFF

BC9000 - BECKHOFF
Stok Durumu: İkinci El
Marka: Beckhoff
Ürün Kodu: BC9000
Stok Miktarı: Stok Sorunuz
0 yorum  0 yorum  |  Yorum Yap

BC9000, BC9050 | Ethernet TCP/IP Bus Terminal Controllers

The Bus Terminal Controller is programmed using the TwinCAT programming system according to IEC 61131-3. The configuration/programming interface of the BC9000 or BC9050 is used for loading the PLC program. If the software PLC TwinCAT is in use, the PLC program can also be loaded via Ethernet.

In the default setting the inputs and outputs of the connected Bus Terminals are assigned to the controller. Each Bus Terminal can be configured in such a way that it exchanges data directly through the fieldbus with the higher-level automation device.

Controller for distributed signal processing

The BC9000 and BC9050 Bus Terminal Controllers support the operation of all Bus Terminal types. As far as the user is concerned, the inputs and outputs are not handled any differently from the way they are by other coupler series. The information is made available for use as a byte array in the process image of the automation device.

The analog and multi-functional Bus Terminals can be adapted to each specific application using the KS2000 configuration set. Depending on the type, the analog Bus Terminals' registers contain temperature ranges, gain values and linearisation characteristics. With the KS2000, the required parameters can be set on a PC. The Bus Terminals store settings permanently and in a fail-safe manner.

Having the controller (PLC, IPC) carry out the configuration of the Bus Terminals is a further option. The PLC or IPC uses function blocks (FB) to take care of the configuration of all the peripherals during the start-up phase. The controller can, if required, upload the non-centrally generated configuration data in order to manage and store them centrally. This means that it is not necessary to carry out the setting procedure again if a Bus Terminal is exchanged. The controller carries out the desired setting automatically after switching on.

PLC data Ethernet TCP/IP | BC9000 BC9050
Programming via TwinCAT and programming interface or Ethernet
Program memory 64/96 kbytes 48 kbytes
Data memory 64/128 kbytes 32 kbytes
Remanent data 4,080 bytes 2 kbytes
Runtime system 1 PLC task
PLC cycle time approx. 1.5 ms for 1,000 instructions (without I/O cycle, K-bus)
Programming languages IEC 61131-3 (IL, LD, FBD, SFC, ST)
Online change yes
Technical data BC9000 BC9050
Number of Bus Terminals 64 64 (255 with K-bus extension)
Max. number of bytes fieldbus 512 byte input and 512 byte output
Max. number of bytes process image 512 byte input and 512 byte output 2,048 byte input and 2,048 byte output
Digital peripheral signals 512 inputs/outputs 2,040 inputs/outputs
Analog peripheral signals 128 inputs/outputs 512 inputs/outputs
Protocol TwinCAT ADS, Modbus TCP
Configuration possibility via KS2000 or Ethernet
Data transfer rates 10/100 Mbaud, automatic recognition of the transmission rate
Bus interface 1 x RJ 45
Power supply 24 V DC (-15 %/+20 %)
Input current 70 mA + (total K-bus current)/4, 500 mA max. 320 mA max.
Starting current 2.5 x continuous current
Recommended fuse ≤ 10 A
Current supply K-bus 1,750 mA 1,000 mA
Power contacts 24 V DC max./10 A max.
Electrical isolation 500 V (power contact/supply voltage/fieldbus)
Weight approx. 170 g approx. 100 g
Operating/storage temperature -25…+60 °C/-40…+85 °C 0…+55 °C/-25…+85 °C
Protect. class/installation pos. IP 20/variable
Approvals CE, UL, Ex, GL CE, UL, Ex